[1]劉彥琴,劉君,周波,等.聲電聯合法在主變局放缺陷定位中的現場應用[J].高壓電器,2018,54(11):239-244.[doi:10.13296/j.1001-1609.hva.2018.11.035]
 LIU Yanqin,LIU Jun,ZHOU Bo,et al.Field Application of Acoustic-electrical Combination Method in the PD DefectLocation of Main Transformer[J].High Voltage Apparatus,2018,54(11):239-244.[doi:10.13296/j.1001-1609.hva.2018.11.035]
點擊複制

聲電聯合法在主變局放缺陷定位中的現場應用()
分享到:

《高壓電器》[ISSN:1001-1609/CN:61-11271/TM]

卷:
第54卷
期數:
2018年11期
頁碼:
239-244
欄目:
電力變壓器局部放電檢測及狀態評估
出版日期:
2018-11-05

文章信息/Info

Title:
Field Application of Acoustic-electrical Combination Method in the PD Defect Location of Main Transformer
作者:
劉彥琴劉君周波宋穎郭超程鵬高竣胡琳
國網四川電力成都供電公司, 成都 610000
Author(s):
LIU Yanqin LIU Jun ZHOU Bo SONG Ying GUO Chao CHENG Peng GAO Jun HU Lin
State Grid Sichuan Electric Power Chengdu Power Supply Company, Chengdu 610000, China
關鍵詞:
主變 局部放電 定位 聲電聯合法
Keywords:
main transformer PD location acoustic-electrical combination method
DOI:
10.13296/j.1001-1609.hva.2018.11.035
文獻標志碼:
A
摘要:
文中介紹了聲電聯合法在成都某110 kV變電站1號主變局放檢測及定位中的現場應用案例。針對驗收試驗中發現的異常放電信號,首先利用檢測阻抗法進行一次定位分析,確定放電源所處的大致範圍。其次,基于局部放電的聲電信號不同的傳播特性,結合超聲波測試技術,采用聲電聯合法對放電源進行二次精確定位。最後,通過對缺陷處理後的局放信號進行複測以及有限元仿真,驗證了聲電聯合法在現場主變局放定位中的准確性和有效性。
Abstract:
In this paper,a field application case of the acoustic-electrical combination method in partial discharge(PD)detection and localization of No.1 transformer in a 110 kV substation in Chengdu is introduced. For the abnormal discharge signal found in the acceptance test,a rough location is first performed using the detection impedance method to determine the approximate range of the discharge source. Secondly,based on the different propagation characteristics of acoustic-electrical signals of PD, and combined with ultrasonic testing technology, an acoustic-electric combination method is used to perform secondary accurate localization of the discharge source. Finally, the repetitive measurement of the PD signal after the defect processing and finite element method are performed to verify the accuracy and effectiveness of the acoustic-electrical combination method in the PD location of the transformer.

參考文獻/References:

[1] 楊麗君,廖瑞金,孫才新,等. 油紙絕緣的局部放電特征量分析及危險等級評估方法研究[J]. 中國電機工程學報,2011,31(1):123-130.
YANG Lijun,LIAO Ruijin,SUN Caixin,et al. Partial discharge characteristics and risk assessment method for oil-paper[J]. Proceedings of the CSEE,2011,31(1):123-130.
[2] 高 竣,廖瑞金,王有元,等. 油紙絕緣水分平衡樣品的制備及水分評估頻域特征量提取[J]. 電工技術學報,2015,30(18):196-202.
GAO Jun,LIAO Ruijin,WANG Youyuan,et al. Preparation of oil-paper insulation samples with moisture equilibrium and frequency domain characteristic parameters extraction for moisture assessment[J]. Transactions of China Electrotechnical Society,2015,30(18):196-202.
[3] 劉君華,姚 明,黃成軍,等. 采用聲電聯合法的GIS局部放電定位試驗研究[J]. 高電壓技術,2009,35(10):2458-2463.
LIU Junhua,YAO Ming,HUANG Chengjun,et al. Experimental research on partial discharge localization in GIS using ultrasonic associated with electromagnetic wave method[J]. High Voltage Engineering,2009,35(10):2458-2463.
[4] 周力行,何 蕾,李衛國. 變壓器局部放電超聲信號特性及放電源定位[J]. 高電壓技術,2003,29(5):11-13.
ZHOU Lihang,HE Lei,LI Weiguo. Research on characteristics of ultrasonic signal of partial discharge and partial discharge sources location in transformer[J]. High Voltage Engineering,2003,29(5):11-13.
[5] 王國利,郝豔捧,李彥明. 電力變壓器局部放電定位方法的現狀和前景[J]. 變壓器,2001,38(11):22-27.
WANG Guoli,HAO Yanpeng,LI Yanming. Present situation and prospect of PD location method used in power transformers[J]. Transformer,2001,38(11):22-27.
[6] LUNDGAARD L E. Partial discharge,XIII:Acoustic partial discharge detection-fundamental consideration[J]. IEEE Electrical Insulation Magazine,1992,8(4):25-31.
[7] 章 濤,王俊波,李國偉. 10 kV開關櫃局部放電檢測技術研究與運用[J]. 高壓電器,2012,48(10):100-104.
ZHANG Tao,WANG Junbo,LI Guowei. Research on the partial discharge detection technology for 10 kV switchgear[J]. High Voltage Apparatus,2012,48(10):100-104.
[8] 王俊波,徐 鑫,李國偉,等. 高壓開關櫃局部放電聲電聯合定位檢測技術[J]. 無損檢測,2018,40(1):72-74.
WANG Junbo,XU Xin,LI Guowei,et al. Electroacoustic detection and location technology in partial discharge of high voltage switchgear[J]. Non-Destructive Testing,2018,40(1):72-74.
[9] 孫 焱. 開關櫃聲電聯合局部放電檢測在晉中電網的應用[D]. 北京:華北電力大學,2015.
SUN Yan. Switchgear acoustoelectric combined application of partial discharge detection in Jingzhong power grid[D]. Beijing:North China Electric Power University,2015.
[10] 胡偉濤. 聲電聯合技術檢測GIS局部放電的試驗[J]. 電力科學與技術學報,2012,27(2):57-64.
HU Weitao. Experimental on partial discharge detection in GIS using ultrasonic associated with electromagnetic wave method[J]. Journal of Electric Power Science and Technology,2012,27(2):57-64.
[11] 倪宏坤,王立晶. 聲電聯合檢測技術在GIS中的應用[J]. 國網技術學院學報,2016,19(5):31-35.
NI Hongkun,WANG Lijing. Application of a joint test using ultrasonic associated with electromagnetic wave in GIS[J]. Journal of Shandong Electric Power College,2016,19(5):31-35.
[12] 趙廷志,陳仁剛,馮新岩,等. 基于聲電聯合法的GIS局部放電檢測分析[J]. 山東電力技術,2016,43(9):35-38.
ZHAO Tingzhi,CHEN Rengang,FENG Xinyan,et al. Detection analysis of GIS partial discharge based on acoustic-electric method[J]. Shandong Electric Power,2016,43(9):35-38.
[13] 宋蓓華. 基于聲電聯合的GIS局部放電帶電檢測技術研究[D]. 上海:上海交通大學,2012.
SONG Beihua. Based on the UHF and AE combined GIS partial discharge on-line detection technology research[D]. Shanghai:Shanghai Jiao Tong University,2012.
[14] 師青梅,皮 偉,左 晶,等. 應用超聲光柵測量變壓器油中超聲波速度[J]. 物理與工程,2011,21(5):28-30.
SHI Qingmei,PI Wei,ZUO Jing,et al. The measurement of ultrasonic velocity in transformer oil with ultrasonic grating[J]. Physics and Engineering,2011,21(5):28-30.
[15] GUBANSKI S M,BLENNOW J,HOLMGREN B,et al. Dielectric response diagnoses for transformer windings[R]. Paris:Report of CIGRE TF D1.01.14 Technical Brochure 414,2010.

備注/Memo

備注/Memo:
收稿日期:2018-04-06; 修回日期:2018-06-21.劉彥琴(1982—),女,碩士,高級工程師,主要研究方向爲電測、熱工技術等。 劉 君(1984—),男,博士,高級工程師,主要研究方向爲變壓器絕緣老化機制及其狀態評估方面。 周 波(1984—),男,碩士,高級工程師,主要研究方向爲電氣設備狀態監測與故障診斷。 宋 穎(1984—),男,碩士,工程師,主要研究方向爲變電檢修、電氣試驗等。 郭 超(1988—),男,博士,高級工程師,主要研究方向爲電氣設備狀態監測與故障診斷。 程 鵬(1987—),男,博士,工程師,主要研究方向爲多物理耦合場數值計算、電氣設備狀態監測與故障診斷。 高 竣(1989—),男,博士,工程師,主要研究方向爲電氣設備狀態監測與故障診斷(通訊作者)。 胡 琳(1984—),男,本科,工程師,主要研究方向爲電氣設備狀態監測與故障診斷。